1. Applications
2. Description
|
Item
|
Details
|
|---|---|
|
Product Model
|
AACSR-ANT-COL-TRA-HGH
|
|
Conductor Type
|
Anti-Icing All Aluminum Alloy Conductor Steel Reinforced for High-Altitude Cold Region Transmission Lines
|
|
Aluminum Alloy Strand Grade
|
High-Strength Al-Zr Alloy + Dual-Layer Nano Ice-Phobic Coating (Tensile Strength ≥320MPa, Ice Accumulation -60% vs Conventional AACSR)
|
|
Steel Core Grade
|
High-Tensile Galvanized Steel Wire (Tensile Strength ≥1570MPa, Low-Temperature Anti-Brittle Treatment)
|
|
Stranding Structure
|
Optimized Anti-Icing Concentric Stranding, Wind-Enhanced Design, Alternate Left-Right Lay Direction
|
|
Standard Compliance
|
GB/T 1179, IEC 61089, ASTM B399, EN 50182, IEC 60865 (Ice Load Test)
|
|
Rated Voltage
|
10kV-220kV (Medium to High Voltage)
|
|
Operating Temperature Range
|
-55ºC to 90ºC (Long-Term Operation at -45ºC to 80ºC)
|
|
Overall Tensile Strength
|
≥490MPa
|
|
Anti-Icing Performance
|
Ice Accumulation Weight Reduced by 60%; Ice-Adhesion Strength ≤0.2N/mm²; Pass -40ºC Ice Coating Test
|
|
Applicable Span
|
30m-120m (High-Altitude Cold Region Medium-Long Span Transmission Lines)
|
|
Environmental Adaptability
|
Adapt to High Altitude (≥3000m), Extreme Low Temperature, Freeze-Thaw Cycles, Wind-Snow Icing & High-Altitude Corrosion
|
|
Service Life
|
45-55 Years (In High-Altitude Cold Region Environment)
|
|
Quality Certification
|
ISO 9001, ISO 14001, SGS/BV Third-Party Anti-Icing, Low-Temperature Mechanical & Electrical Performance Test
|
|
Parameter Category
|
Parameter Name
|
Technical Details
|
Buyer Selection Guidelines
|
|---|---|---|---|
|
Electrical Performance
|
Electrical Conductivity
|
≥58% IACS
|
High conductivity ensures low transmission loss for long-distance high-altitude transmission, reducing energy waste and improving project economic benefits.
|
|
DC Resistivity (20ºC)
|
≤0.0310 Ω·mm²/m
|
Low resistivity maintains stable voltage output under extreme low temperatures, avoiding fluctuations that affect high-altitude power supply and grid stability.
|
|
|
Rated Current
|
500A-2000A (Depends on Cross-Section)
|
Match high-altitude cold region load demand: 500-1000A for small alpine power grids, distributed energy; 1000-2000A for large transmission lines, high-altitude wind/photovoltaic grid connection.
|
|
|
Mechanical & Structural Performance
|
Aluminum Alloy Strand Tensile Strength
|
≥320MPa
|
High strength combined with ice-phobic coating resists ice-induced tension and high-altitude wind loads, adapting to alpine harsh mechanical environments.
|
|
Steel Core Tensile Strength
|
≥1570MPa
|
Reinforced steel core with low-temperature toughness prevents conductor breakage caused by ice accumulation, freeze-thaw cycles and high-altitude strong winds.
|
|
|
Elongation at Break (-45ºC)
|
≥10% (Overall Conductor)
|
Excellent low-temperature elongation avoids brittle fracture in extreme cold, ensuring conductor reliability during long-term alpine operation.
|
|
|
Nominal Cross-Section Range
|
185mm²-800mm²
|
185-400mm² for small alpine transmission lines, distributed energy; 400-800mm² for large high-altitude transmission lines, interconnection grids.
|
|
|
Outer Diameter (Typical)
|
185mm²: ≈19.6mm; 400mm²: ≈29.0mm; 800mm²: ≈39.8mm (Tolerance: ±0.3mm)
|
Optimized diameter balances anti-icing performance and wind flow; compatible with standard high-altitude fittings (anti-icing dampers, low-temperature insulators).
|
|
|
Environmental Adaptability & Durability
|
Low-Temperature Resistance
|
Long-Term Operation at -45ºC; No Brittleness or Performance Degradation at -55ºC
|
Suitable for ultra-low temperature high-altitude areas, avoiding conductor damage caused by extreme cold and ensuring year-round stable operation.
|
|
Freeze-Thaw Resistance
|
Pass 500 Cycles of Freeze-Thaw Test (-40ºC to 20ºC); No Structural Damage
|
Adapts to frequent freeze-thaw cycles in alpine permafrost regions, extending conductor service life and reducing maintenance.
|
|
|
High-Altitude Corrosion Resistance
|
Ice-Phobic Coating + Galvanized Steel Core; Pass 4000h Salt Spray Test
|
Resists high-altitude salt mist, humid air and frost corrosion, ensuring durability in high-altitude harsh atmospheric environments.
|
|
|
Length Per Roll
|
185-400mm²: 1000m/roll; 800mm²: 500m/roll (Customizable for Bulk Orders)
|
1000m/roll for large-scale high-altitude transmission projects; 500m/roll for maintenance and small-section line upgrades in remote alpine areas.
|
HENAN UME CABLE CO., LTD has a strict quality control policy in every step from the order to After-sales service!
Production:

Q1: Are you a manufacturer?
Yes, we are the manufacturer.
Q2: What are your main products?
Our products range as follows:
1. Electrical wire/PVC Building Wires.
2. PVC/XLPE insulated Power Cables up to 110kv.
3. Overhead Aerial Bundle Cable/ABC Cables.
4. Bare Conductors, like AAC, AAAC, ACSR, ACAR, ASCR/AW, and so on.
5. Steel wire/strand-like EHS, GSW and ACS(Aluminum Clad Steel), CCS(Copper Clad Steel).
6. Rubber Cables, Mining Cables, Welding Cable, and Control Cables.
7. Concentric Cables with Copper/Aluminum/Aluminum Alloy 8000s' Conductor.
Q3: Do you provide samples? Is it free or extra?
Yes, we could offer the samples for free
Q4: Is the quality of your products guaranteed?
We have passed ISO9001, ISO14001, ISO45001, and all our products have CE certificates.
Q5: Which markets do you involve mainly in?
Our products have been exported mainly to Africa, the Middle East, Southeast Asia, South America, Central America, North America, Europe, Australia, etc.
Q6: What is your payment term?
T/T or L/C
Q7: What about the delivery time?
Generally, it is 3-7days if the goods are in stock. Or it is 7-30days if the goods are not in stock, it is according to quantity.