Type: | Insulated |
---|---|
Conductor Type: | Solid Strand |
Application: | Overhead |
Still deciding? Get samples of US$ 1/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
ONE-STOP SOLUTIONS FOR WIRES&CABLES - HENAN UME CABLE CO., LTD
Over 30 years of Wires and Cables manufacture experience and Export to over 50 countries.
1. Application
The flame-retardant type cables are not easy to burn or their flame propagation is limited only in a certain length. These cables are suitable for high installation density places like power station, subway, tunnels, high-building, large industrial enterprise, oil field and mine etc.
2. Construction
Long-time permissible operation temperature is 70ºC.
Max.short-circuit(not more than 5 sec.) temperature of conductor shall not be higher than 160ºC. Ambient temperature of installation is not lower than 0ºC
3. Standard
IEC 60502, BS, DIN, ASTM, GB12706-2008
LV Power Cables - Copper Conductor IEC 60502-1 | ||
PVC Insulated Cable | VV (NYY) | CU/PVC/PVC |
VY (NY2Y) | CU/PVC/PE | |
VV22 (NYBY) | CU/PVC/STA/PVC | |
VV23 (NYB2Y) | CU/PVC/STA/PE | |
VV32 (NYRY) | CU/PVC/SWA/PVC | |
VV33 (NYR2Y) | CU/PVC/SWA/PE | |
LV Power Cables - Aluminum Conductor IEC 60502-1 | ||
PVC Insulated Cable | VLV (NAYY) | AL/PVC/PVC |
VLY (NAY2Y) | AL/PVC/PE | |
VLV22 (NAYBY) | AL/PVC/STA/PVC | |
VLV22 (NAYB2Y) | AL/PVC/STA/PE | |
VLV32 (NAYRY) | AL/PVC/SWA/PVC | |
VLV33 (NAYR2Y) | AL/PVC/SWA/PE |
Nom. Cross-section of conductor | Strands No./Dia. Of Conductor | Insulation Thickness | Sheath Thickness | Approx. O.D. | Approx.Weight | Max. D.C Resistance of Conductor (20 ºC) | Testing Voltage A.C | Current Rating | |
mm2 | pc/mm | mm | mm | (mm) | kg/km | Ω /km | kV/5min | In air (A) | In soil(A) |
1 × 25 | 7/2.14 | 3.4 | 2 | 20.0 | 598 | 0.727 | 21 | 140 | 150 |
1 × 35 | 7/2.52 | 3.4 | 2 | 22.0 | 719 | 0.524 | 21 | 175 | 180 |
1 × 50 | 10/2.52 | 3.4 | 2 | 23.0 | 884 | 0.387 | 21 | 205 | 215 |
1 × 70 | 14/2.52 | 3.4 | 2 | 24.0 | 1097 | 0.268 | 21 | 260 | 265 |
1 × 95 | 19/2.52 | 3.4 | 2 | 26.0 | 1378 | 0.193 | 21 | 315 | 315 |
1 × 120 | 24/2.52 | 3.4 | 2 | 28.0 | 1658 | 0.153 | 21 | 365 | 360 |
1 × 150 | 30/2.52 | 3.4 | 2 | 30.0 | 1967 | 0.124 | 21 | 415 | 405 |
1 × 185 | 37/2.52 | 3.4 | 2 | 31.0 | 2335 | 0.0991 | 21 | 475 | 455 |
1 × 240 | 48/2.52 | 3.4 | 2 | 34.0 | 2908 | 0.0754 | 21 | 565 | 530 |
1 × 300 | 61/2.52 | 3.4 | 2 | 36.0 | 3507 | 0.0601 | 21 | 645 | 595 |
1 × 400 | 61/2.97 | 3.4 | 2.5 | 39.0 | 4503 | 0.0470 | 21 | 750 | 680 |
1 × 500 | 61/3.23 | 3.4 | 2.5 | 42.0 | 5479 | 0.0366 | 21 | 865 | 765 |
1 × 630 | 61/3.50 | 3.4 | 2.5 | 48.0 | 6952 | 0.0283 | 21 | 990 | 860 |
1 × 800 | 91/3.20 | 3.4 | 2.6 | 52.0 | 7120 | 0.0221 | 21 | 1140 | 950 |
1 × 1000 | 91/3.75 | 3.4 | 2.8 | 57.0 | 10500 | 0.0176 | 21 | 1250 | 1040 |
3 × 25 | 7/2.14 | 3.4 | 2.3 | 41.0 | 895 | 0.727 | 21 | 120 | 125 |
3 × 35 | 7/2.52 | 3.4 | 2.4 | 44.0 | 2293 | 0.524 | 21 | 145 | 155 |
3 × 50 | 10/2.52 | 3.4 | 2.5 | 46.0 | 2812 | 0.387 | 21 | 175 | 180 |
3 × 70 | 14/2.52 | 3.4 | 2.6 | 50.0 | 3508 | 0.268 | 21 | 220 | 220 |
3 × 95 | 19/2.52 | 3.4 | 2.7 | 53.0 | 4402 | 0.193 | 21 | 265 | 265 |
3 × 120 | 24/2.52 | 3.4 | 2.8 | 56.0 | 5319 | 0.153 | 21 | 305 | 300 |
3 × 150 | 30/2.52 | 3.4 | 2.9 | 59.0 | 6309 | 0.124 | 21 | 350 | 340 |
3 × 185 | 37/2.52 | 3.4 | 3.0 | 62.0 | 7319 | 0.0991 | 21 | 395 | 380 |
3 × 240 | 48/2.52 | 3.4 | 3.2 | 68.0 | 9218 | 0.0754 | 21 | 470 | 435 |
3 × 300 | 61/2.52 | 3.4 | 3.4 | 72.0 | 11159 | 0.0601 | 21 | 535 | 485 |
3 × 400 | 61/2.97 | 3.4 | 3.6 | 81.0 | 15107 | 0.0470 | 21 | 610 | 520 |
Nominal cross sectional area of conductor mm2 | Insulation Thickness mm | Sheath Thickness mm | overall diameter of cable mm | Approx.weight of cable kg/km | Max.D.C resistance of conductor ohm/km | Testing voltage A.C kV/min | ||
Cu | Al | Cu | Al | |||||
1X2.5 | 0.7 | 1.4 | 6.1 | 57 | 41 | 7.41 | 12.1 | 3.5 |
1X4 | 0.7 | 1.4 | 6.6 | 74 | 50 | 4.61 | 7.41 | 3.5 |
1X6 | 0.7 | 1.4 | 7.1 | 96 | 59 | 3.08 | 4.61 | 3.5 |
1X10 | 0.7 | 1.4 | 8.2 | 138 | 79 | 1.83 | 3.08 | 3.5 |
1X16 | 0.7 | 1.4 | 9.2 | 198 | 103 | 1.15 | 1.91 | 3.5 |
1X25 | 0.9 | 1.4 | 10.7 | 294 | 144 | 0.727 | 1.2 | 3.5 |
1X35 | 0.9 | 1.4 | 11.7 | 387 | 178 | 0.524 | 0.868 | 3.5 |
1X50 | 1 | 1.4 | 13.2 | 510 | 226 | 0.387 | 0.641 | 3.5 |
1X70 | 1.1 | 1.4 | 15.1 | 712 | 302 | 0.268 | 0.443 | 3.5 |
1X95 | 1.1 | 1.5 | 16.9 | 963 | 395 | 0.193 | 0.32 | 3.5 |
1X120 | 1.2 | 1.5 | 18.5 | 1197 | 480 | 0.153 | 0.253 | 3.5 |
1X150 | 1.4 | 1.6 | 20.7 | 1476 | 591 | 0.124 | 0.206 | 3.5 |
1X185 | 1.6 | 1.6 | 22.8 | 1829 | 722 | 0.0991 | 0.164 | 3.5 |
1X240 | 1.7 | 1.7 | 25.4 | 2375 | 920 | 0.0754 | 0.125 | 3.5 |
1X300 | 1.8 | 1.8 | 28 | 2957 | 1131 | 0.0601 | 0.1 | 3.5 |
1X400 | 2 | 1.9 | 31.6 | 3762 | 1428 | 0.047 | 0.0778 | 3.5 |
1X500 | 2.2 | 2 | 35.1 | 4795 | 1798 | 0.0366 | 0.0605 | 3.5 |
1X630 | 2.4 | 2.2 | 39.3 | 6171 | 2295 | 0.0283 | 0.0469 | 3.5 |
Cross-sectional Area (mm²) | No. &diameter of wire (N/mm) | Average overall diameter (mm) | Reference weight (kg/km) | Conductor Resistance (Ω/km) |
20ºC Max | ||||
1.5 | 1/1.38 | 5.6 | 44 | 12.1 |
2.5 | 1/1.76 | 6 | 56 | 7.41 |
4 | 7/0.85 | 6.8 | 78 | 4.61 |
6 | 7/1.04 | 7.4 | 101 | 3.08 |
10 | 7/1.35 | 8.3 | 146 | 1.83 |
16 | 7/1.70 | 9.3 | 209 | 1.15 |
25 | 7/2.14 | 11 | 312 | 0.727 |
35 | 19/1.53 | 12.3 | 412 | 0.524 |
50 | 19/1.78 | 13.7 | 539 | 0.387 |
70 | 19/2.14 | 15.9 | 761 | 0.268 |
95 | 19/2.52 | 17.8 | 1022 | 0.193 |
120 | 37/2.03 | 19.8 | 1282 | 0.153 |
150 | 37/2.25 | 22 | 1575 | 0.124 |
185 | 37/2.52 | 24.5 | 1967 | 0.0991 |
240 | 61/2.25 | 27.3 | 2534 | 0.0754 |
300 | 61/2.52 | 30.1 | 3152 | 0.0601 |
400 | 91/2.36 | 34.2 | 4103 | 0.047 |
500 | 91/2.65 | 38 | 5141 | 0.0366 |
630 | 127/2.52 | 42.2 | 6439 | 0.0283 |
800 | 127/2.85 | 47.3 | 8199 | 0.0221 |
1000 | 127/3.15 | 52 | 9986 | 0.0176 |
HENAN UME CABLE CO., LTD has a strict quality control policy in every step from the order to After-sales service!
Production:
Q1: Are you a manufacturer?
Yes, we are the manufacturer.
Q2: What are your main products?
Our products range as follows:
1. Electrical wire/PVC Building Wires.
2. PVC/XLPE insulated Power Cables up to 110kv.
3. Overhead Aerial Bundle Cable/ABC Cables.
4. Bare Conductors, like AAC, AAAC, ACSR, ACAR, ASCR/AW, and so on.
5. Steel wire/strand-like EHS, GSW and ACS(Aluminum Clad Steel), CCS(Copper Clad Steel).
6. Rubber Cables, Mining Cables, Welding Cable, and Control Cables.
7. Concentric Cables with Copper/Aluminum/Aluminum Alloy 8000s' Conductor.
Q3: Do you provide samples? Is it free or extra?
Yes, we could offer the samples for free
Q4: Is the quality of your products guaranteed?
We have passed ISO9001, ISO14001, ISO45001, and all our products have CE certificates.
Q5: Which markets do you involve mainly in?
Our products have been exported mainly to Africa, the Middle East, Southeast Asia, South America, Central America, North America, Europe, Australia, etc.
Q6: What is your payment term?
T/T or L/C
Q7: What about the delivery time?
Generally, it is 3-7days if the goods are in stock. Or it is 7-30days if the goods are not in stock, it is according to quantity.