Applications
AAC are used in overhead power transmission and distribution lines with various grade voltages. Under the same weight,AAC is with higher DC resistance and lower cost than copper conductor. Aluminum is light and is easy to lay.
Standard
ASTM B231 B232, BS 215 , DIN 48201, CSA C49,NFC 34120
Specification
Stranded 1350 aluminum conductors shown in this section of data are classified, as follows:
Class AA | For bare conductors usually used in overhead lines. |
Class A | For conductors to be covered with weather-resistant materials and for bare conductors where greater flexibility is required. |
Class B | For conductors to be insulated with various materials and for conductors indicated under Class A where greater flexibility is required. |
Class C | For conductors where greater flexibility is required |
Code word | Size of Conductor | Stranding and Wire Diameter | Overall Diameter | Max.D.C. Resistance at 20°C | Code word | Size of Conductor | Stranding and Wire Diameter | Overall Diameter | Max.D.C. Resistance at 20°C |
AWG or MCM | mm | mm | ohm/km | AWG or MCM | mm | mm | ohm/km | ||
Peachbell | 6 | 7/1.554 | 4.67 | 2.1692 | Verbena | 700 | 37/3.493 | 24.45 | 0.0813 |
Rose | 4 | 7/1.961 | 5.89 | 1.3624 | Nasturtium | 715.5 | 61/2.75 | 24.76 | 0.0795 |
Lris | 2 | 7/2.474 | 7.42 | 0.8577 | Violet | 715.5 | 37/3.533 | 24.74 | 0.0795 |
Pansey | 1 | 7/2.776 | 8.33 | 0.6801 | Cattail | 750 | 61/2.817 | 25.35 | 0.0759 |
Poppy | 1/0 | 7/3.119 | 9.36 | 0.539 | Petunia | 750 | 37/3.617 | 25.32 | 0.0759 |
Aster | 2/0 | 7/3.503 | 10.51 | 0.4276 | Lilac | 795 | 61/2.90 | 26.11 | 0.0715 |
Phlox | 3/0 | 7/3.932 | 11.8 | 0.339 | Arbutus | 795 | 37/3.724 | 26.06 | 0.0715 |
Oxlip | 4/0 | 7/4.417 | 13.26 | 0.2688 | Snapdragon | 900 | 61/3.086 | 27.78 | 0.0632 |
Valerian | 250 | 19/2.913 | 14.57 | 0.2275 | Cockscomb | 900 | 37/3.962 | 27.73 | 0.0632 |
Sneezewort | 250 | 7/4.80 | 14.4 | 0.2275 | Goldenrod | 954 | 61/3.177 | 28.6 | 0.0596 |
Laurel | 266.8 | 19/3.01 | 15.05 | 0.2133 | Magnolia | 954 | 37/4.079 | 28.55 | 0.0596 |
Daisy | 266.8 | 7/4.96 | 14.9 | 0.2133 | Camellia | 1000 | 61/3.251 | 29.36 | 0.0569 |
Peony | 300 | 19/3.193 | 15.97 | 0.1896 | Hawkweed | 1000 | 37/4.176 | 29.23 | 0.0569 |
Tulip | 336.4 | 19/3.381 | 16.91 | 0.1691 | Larkspur | 1033.5 | 61/3.307 | 29.76 | 0.055 |
Daffodil | 350 | 19/3.447 | 17.24 | 0.1625 | Bluebell | 1033.5 | 37/4.244 | 29.72 | 0.055 |
Canna | 397.5 | 19/3.673 | 18.36 | 0.1431 | Marigold | 1113 | 61/3.432 | 30.89 | 0.0511 |
Goldentuft | 450 | 19/3.909 | 19.55 | 0.1264 | Hawthorn | 1192.5 | 61/3.551 | 31.05 | 0.0477 |
Syringa | 477 | 37/2.882 | 20.19 | 0.1193 | Narcissus | 1272 | 61/3.668 | 33.02 | 0.0477 |
Cosmos | 477 | 19/4.023 | 20.12 | 0.1193 | Columbine | 1351.5 | 61/3.78 | 34.01 | 0.0421 |
Hyacinth | 500 | 37/2.951 | 20.65 | 0.1138 | Carnation | 1431 | 61/3.89 | 35.03 | 0.0398 |
Zinnia | 500 | 19/4.12 | 20.6 | 0.1138 | Gladiolus | 1510.5 | 61/4.00 | 35.09 | 0.0376 |
Dahlia | 556.5 | 19/4.346 | 21.73 | 0.1022 | Coreopsis | 1590 | 61/4.099 | 36.51 | 0.03568 |
Mistletoe | 556.5 | 37/3.114 | 21.79 | 0.1022 | Jessamine | 1750 | 61/4.302 | 38.72 | 0.0325 |
Meadowsweet | 600 | 37/3.233 | 22.63 | 0.0948 | Cowslip | 2000 | 91/3.76 | 41.4 | 0.02866 |
Orchid | 636 | 37/3.33 | 23.31 | 0.0894 | Lupine | 2500 | 91/4.21 | 46.3 | 0.023 |
Heuchera | 650 | 37/3.366 | 23.56 | 0.0875 | Trillium | 3000 | 127/3.90 | 50.75 | 0.0192 |
Flag | 700 | 61/2.72 | 24.48 | 0.0813 | Bluebonnet | 3500 | 127/4.21 | 54.8 | 0.01653 |
Code name | Nominal aluminum area | Stranding and wire diameter | Sectional area | Overall diameter | Linear mass | Max. DC resistance at 20ºC | Rated strength | Final modulus of elasticity | Coefficient of linear expansion |
mm2 | mm | mm2 | mm | kg/km | Ω/km | daN | hbar | /ºC | |
Midge | 22 | 7/2.06 | 23.33 | 6.18 | 63.8 | 1.227 | 399 | 5900 | 23.0x10-6 |
Aphis | 25 | 3/3.35 | 26.40 | 7.2 | 73 | 1.081 | 411 | 5900 | 23.0x10-6 |
Gnat | 25 | 7/2.21 | 26.8 | 6.6 | 73 | 1.066 | 459 | 5900 | 23.0x10-6 |
Weevil | 30 | 3/3.66 | 31.6 | 7.9 | 86 | 0.9082 | 486 | 5900 | 23.0x10-6 |
Mosquito | 35 | 7/2.59 | 37.0 | 7.8 | 101 | 0.7762 | 603 | 5900 | 23.0x10-6 |
Ladybird | 40 | 7/2.79 | 42.8 | 8.4 | 117 | 0.6689 | 687 | 5900 | 23.0x10-6 |
Ant | 50 | 7/3.10 | 52.83 | 9.30 | 145 | 0.5419 | 828 | 5900 | 23.0x10-6 |
Fly | 60 | 7/3.40 | 63.55 | 10.20 | 174 | 0.4505 | 990 | 5900 | 23.0x10-6 |
Bluebottle | 70 | 7/3.66 | 73.7 | 11.0 | 202 | 0.3881 | 1134 | 5900 | 23.0x10-6 |
Earwig | 75 | 7/3.78 | 78.5 | 11.4 | 215 | 0.3644 | 1194 | 5900 | 23.0x10-6 |
Grasshopper | 80 | 7/3.91 | 84.1 | 11.7 | 230 | 0.3406 | 1278 | 5900 | 23.0x10-6 |
Clegg | 90 | 7/4.17 | 95.6 | 12.5 | 262 | 0.2994 | 1453 | 5900 | 23.0x10-6 |
Wasp | 100 | 7/4.39 | 106.0 | 13.17 | 290 | 0.2702 | 1600 | 5900 | 23.0x10-6 |
Beetle | 100 | 19/2.67 | 106.0 | 13.4 | 293 | 0.2704 | 1742 | 5600 | 23.0x10-6 |
Bee | 125 | 7/4.90 | 132.0 | 14.7 | 361 | 0.2169 | 1944 | 5600 | 23.0x10-6 |
Cricket | 150 | 7/5.36 | 157.9 | 16.1 | 432 | 0.1818 | 2385 | 5600 | 23.0x10-6 |
Hornet | 150 | 19/3.25 | 157.6 | 16.25 | 434 | 0.1825 | 2570 | 5600 | 23.0x10-6 |
Caterpilla | 175 | 19/3.53 | 186 | 17.7 | 512 | 0.1547 | 2863 | 5600 | 23.0x10-6 |
Chafer | 200 | 19/3.78 | 213.2 | 18.9 | 587 | 0.1349 | 3240 | 5600 | 23.0x10-6 |
Spider | 225 | 19/3.99 | 236.9 | 20.0 | 652 | 0.1211 | 3601 | 5600 | 23.0x10-6 |
Cockroach | 250 | 19/4.22 | 265.7 | 21.10 | 731 | 0.1083 | 4040 | 5600 | 23.0x10-6 |
Butterfly | 300 | 19/4.65 | 322.7 | 23.25 | 888 | 0.08916 | 4875 | 5600 | 23.0x10-6 |
Moth | 350 | 19/5.00 | 373.2 | 25.0 | 1027 | 0.07711 | 5637 | 5600 | 23.0x10-6 |
Drone | 350 | 37/3.58 | 373.3 | 25.1 | 1029 | 0.07741 | 5745 | 5600 | 23.0x10-6 |
Locust | 400 | 19/5.36 | 428.5 | 26.8 | 1179 | 0.06710 | 6473 | 5600 | 23.0x10-6 |
Centipede | 400 | 37/3.78 | 415.2 | 26.46 | 1145 | 0.06944 | 6310 | 5600 | 23.0x10-6 |
Maybug | 450 | 37/4.09 | 486.9 | 28.6 | 1342 | 0.05931 | 7401 | 5600 | 23.0x10-6 |
Scorpion | 500 | 37/4.27 | 529.5 | 29.9 | 1460 | 0.05441 | 7998 | 5600 | 23.0x10-6 |
Cicada | 600 | 37/4.65 | 628.6 | 32.6 | 1733 | 0.04588 | 9495 | 5600 | 23.0x10-6 |
Tarantula | 750 | 37/5.23 | 794.6 | 36.6 | 2191 | 0.03627 | 12010 | 5600 | 23.0x10-6 |
Size | Calculated area | Stranding and wire diameter | Overall diameter | Linear mass | Rated strength | Max. DC resistance at 20ºC |
mm2 | mm2 | mm | mm | kg/km | daN | Ω/km |
16 | 15.89 | 7/1.70 | 5.1 | 44 | 290 | 1.8018 |
25 | 24.25 | 7/2.10 | 6.3 | 67 | 425 | 1.1808 |
35 | 34.36 | 7/2.50 | 7.5 | 94 | 585 | 0.8332 |
50 | 49.48 | 7/3.00 | 9.0 | 135 | 810 | 0.5786 |
50 | 48.36 | 19/1.80 | 9.0 | 133 | 860 | 0.5950 |
70 | 65.82 | 19/2.10 | 10.5 | 181 | 1150 | 0.4371 |
95 | 93.27 | 19/2.50 | 12.5 | 256 | 1595 | 0.3084 |
120 | 117.00 | 19/2.80 | 14.0 | 322 | 1910 | 0.2469 |
150 | 147.10 | 37/2.25 | 15.2 | 406 | 2570 | 0.1960 |
185 | 181.60 | 37/2.50 | 17.5 | 501 | 3105 | 0.1587 |
240 | 242.54 | 61/2.25 | 20.2 | 670 | 4015 | 0.1191 |
300 | 299.43 | 61/2.50 | 22.5 | 827 | 4850 | 0.09650 |
400 | 400.14 | 61/2.89 | 26.0 | 1105 | 6190 | 0.07221 |
500 | 499.83 | 61/3.23 | 29.1 | 1381 | 7600 | 0.05781 |
625 | 626.20 | 91/2.96 | 32.6 | 1733 | 9690 | 0.04625 |
800 | 802.10 | 91/3.35 | 36.8 | 2219 | 12055 | 0.03611 |
1000 | 999.71 | 91/3.74 | 41.1 | 2766 | 14845 | 0.02897 |
Cross Section | Number of Stranding Wires | Diameter | Linear Mass | Rated Strength | Max.D.C. Resistance at 20ºC | |
Wires | Conductor | |||||
mm2 | - | mm | mm | kg/km | kN | Ω/km |
10 | 7 | 1.35 | 4.05 | 27.4 | 1.95 | 2.8633 |
16 | 7 | 1.71 | 5.12 | 43.8 | 3.04 | 1.7896 |
25 | 7 | 2.13 | 6.4 | 68.4 | 4.5 | 1.1453 |
40 | 7 | 2.7 | 8.09 | 109.4 | 6.8 | 0.7158 |
63 | 7 | 3.39 | 10.2 | 172.3 | 10.39 | 0.4545 |
100 | 19 | 2.59 | 12.9 | 274.8 | 17 | 0.2877 |
125 | 19 | 2.89 | 14.5 | 343.6 | 21.25 | 0.2302 |
160 | 19 | 3.27 | 16.4 | 439.8 | 26.4 | 0.1798 |
200 | 19 | 3.66 | 18.3 | 549.7 | 32 | 0.1439 |
250 | 19 | 4.09 | 20.5 | 687.1 | 40 | 0.1151 |
315 | 37 | 3.29 | 23 | 867.9 | 51.97 | 0.0916 |
400 | 37 | 3.71 | 26 | 1102 | 64 | 0.0721 |
450 | 37 | 3.94 | 27.5 | 1239.8 | 72 | 0.0641 |
500 | 37 | 4.15 | 29 | 1377.6 | 80 | 0.0577 |
560 | 37 | 4.39 | 30.7 | 1542.9 | 89.6 | 0.0515 |
630 | 61 | 3.63 | 32.6 | 1738.3 | 100.08 | 0.0458 |
710 | 61 | 3.85 | 34.6 | 1959.1 | 113.6 | 0.0407 |
800 | 61 | 4.09 | 36.8 | 2207.4 | 128 | 0.0361 |
900 | 61 | 4.33 | 39 | 2483.3 | 144 | 0.0321 |
1000 | 61 | 4.57 | 41.1 | 2759.2 | 160 | 0.0289 |
1120 | 91 | 3.96 | 43.5 | 3093.5 | 179.2 | 0.0258 |
1250 | 91 | 4.18 | 46 | 3452.6 | 200 | 0.0231 |
1400 | 91 | 4.43 | 48.7 | 3866.9 | 224 | 0.0207 |
1500 | 91 | 4.58 | 50.4 | 4143.1 | 240 | 0.0193 |
Q1: Are you a manufacturer?
Yes, we are the manufacturer.
Q2: What are your main products?
Our produts range as follows:
1. Electrical wire/PVC Building Wires.
2. PVC/XLPE insulated Power Cables up to 110kv.
3. Overhead Aerial Bundle Cable/ABC Cables.
4. Bare Conductors, like AAC, AAAC, ACSR, ACAR, ASCR/AW, and so on.
5. Steel wire/strand-like EHS, GSW and ACS(Aluminum Clad Steel), CCS(Copper Clad Steel).
6. Rubber Cables, Mining Cables, Welding Cable, and Control Cables.
7. Concentric Cables with Copper/Aluminum/Aluminum Alloy 8000s' Conductor.
Q3: Do you provide samples? Is it free or extra?
Yes, we could offer the samples for free.
Q4: Is the quality of your products guaranteed?
We have passed ISO9001, ISO14001, ISO45001, and all our products have CE certificates.
Q5: Which markets do you involve mainly in?
Our products have been exported mainly to Africa, the Middle East, Southeast Asia, South America, Central America, North America, Europe, Australia, etc.
Q6: What is your payment term?
T/T or L/C.
Q7: What about the delivery time?
Generally, it is 3-7days if the goods are in stock. Or it is 7-30days if the goods are not in stock, it is according to quantity.