Type: | Insulated |
---|---|
Conductor Type: | Solid Strand Flexible |
Application: | Overhead |
Still deciding? Get samples of US$ 1/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
ONE-STOP SOLUTIONS FOR WIRES&CABLES - HENAN UME CABLE CO., LTD
Over 30 years of Wires and Cables manufacture experience and Export to over 50 countries.
1. Application
NYY Cable refers to pvc insulated, pvc sheathed power cable with rated voltage 0.6/1kv, These cables are used for electricity supply in low voltage installation system. They are suitable for installation in indoors and outdoors, in cable ducts, under ground, in power and switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.
2. Construction
Conductor:
Copper or Aluminium conductor, round standed or Shaped, Class 2 to IEC 60228, BS EN 60228. For smaller sizes, a solid round conductor, Class 1 as per IEC 60228, BS EN 60228 can also be supplied upon request.
Insulation:
PVC Insulation material and thickness shall be as per IEC 60502-1 and BS 6346. PVC material shall be Type A as per IEC 60502-1 or TI1 as per BS EN 50363. PVC Insulation material as per SASO 1694 rated for 85°C continuous operation is also available upon special request.
Assembly/Inner Sheath:
Two, Three or Four insulated conductors are laid-up together with non-hygroscopic fillers and the assembly is bedded with an extruded layer of PVC. In case of non- armoured cables, this layer may be omitted
Fire Performance of Cable Sheaths:
Cables can be supplied with special flame retardant PVC outer sheath to comply with the flame test requirements of IEC 60332-3-22, IEC 60332-3-23 and IEC 60332-3-24, can also supply cables with Low Smoke Halogen Free (LSHF) material according to IEC 60502-1, BS 7211, BS 6724 or other equivalent standards.
Nominal Cross Section | Diameter of Conductor (Approx.) | Nominal Insulation Thickness | Nominal PVC Sheath Thickness | Overall Diameter (Approx.) | Weight of Cable (Approx.) |
mm | mm | mm | mm | mm | Kg/Km |
1x4 | 2.25 | 1 | 1.4 | 7.5 | 95 |
1x6 | 2.76 | 1 | 1.4 | 8 | 120 |
1x10 | 4 | 1 | 1.4 | 9 | 165 |
1x16 | 5 | 1 | 1.4 | 10 | 230 |
1x25 | 6.3 | 1.2 | 1.4 | 12 | 340 |
1x35 | 7.4 | 1.2 | 1.4 | 13 | 450 |
1x50 | 8.8 | 1.4 | 1.4 | 14.5 | 570 |
1x70 | 10.6 | 1.4 | 1.4 | 16 | 800 |
1x95 | 12.4 | 1.6 | 1.5 | 18.5 | 1070 |
1x120 | 14 | 1.6 | 1.5 | 20 | 1200 |
1x150 | 15.5 | 1.8 | 1.6 | 22 | 1600 |
1x185 | 17.4 | 2 | 1.7 | 24 | 1980 |
1x240 | 20.3 | 2.2 | 1.7 | 27 | 2560 |
1x300 | 22.7 | 2.4 | 1.8 | 30 | 3180 |
1x400 | 25.4 | 2.6 | 1.9 | 33 | 4060 |
1x500 | 28.8 | 2.8 | 2 | 37 | 5140 |
1x630 | 30.4 | 2.8 | 2.2 | 42 | 6600 |
Nominal Cross Section | Diameter of Conductor (Approx.) | Nominal Insulation Thickness | Nominal PVC Sheath Thickness | Overall Diameter (Approx.) | Weight of Cable (Approx.) |
mm | mm | mm | mm | mm | Kg/Km |
2x1.5 | 1.38 | 0.8 | 1.8 | 12 | 205 |
2x2.5 | 1.76 | 0.8 | 1.8 | 13 | 250 |
2x4 | 2.25 | 1 | 1.8 | 15 | 330 |
2x6 | 2.76 | 1 | 1.8 | 16 | 400 |
2x10 | 4 | 1 | 1.8 | 17.5 | 525 |
2x16 | 5 | 1 | 1.8 | 20 | 720 |
2x25 | 6.3 | 1.2 | 1.8 | 23.5 | 1030 |
2x35 | 7.4 | 1.2 | 1.8 | 25.5 | 1320 |
2x50 | 8.8 | 1.4 | 1.8 | 28.5 | 1670 |
2x70 | 10.6 | 1.4 | 1.8 | 32 | 2290 |
2x95 | 12.4 | 1.6 | 1.9 | 37 | 3060 |
2x120 | 14 | 1.6 | 2 | 40 | 3700 |
2x150 | 15.5 | 1.8 | 2.2 | 44 | 4500 |
2x185 | 17.4 | 2 | 2.3 | 48 | 5570 |
2x240 | 20.3 | 2.2 | 2.5 | 55 | 7180 |
Nominal Cross Section | Diameter of Conductor (Approx.) | Nominal Insulation Thickness | Nominal PVC Sheath Thickness | Overall Diameter (Approx.) | Weight of Cable (Approx.) | ||
mm² | (3)mm | (1)mm | (3)mm | (1)mm | mm | mm | Kg/Km |
3x16/10 | 5 | 4 | 1 | 1 | 1.8 | 22 | 1000 |
3x25/16 | 6.3 | 5 | 1.2 | 1 | 1.8 | 26 | 1460 |
3x 35/16 | 7.4 | 5 | 1.2 | 1 | 1.8 | 28 | 1830 |
3x 50/25 | 8.8 | 6.3 | 1.4 | 1 | 1.8 | 32 | 2410 |
3x 70/35 | 10.6 | 7.4 | 1.4 | 1.2 | 1.9 | 36 | 3360 |
3x 95/50 | 12.4 | 8.8 | 1.6 | 1.2 | 2.1 | 41 | 4440 |
3x120/70 | 14 | 10.6 | 1.6 | 1.4 | 2.2 | 46 | 5580 |
3x150/70 | 15.5 | 10.6 | 1.4 | 1.4 | 2.3 | 49 | 6580 |
3x185/95 | 17.4 | 12.4 | 1.6 | 1.2 | 2.5 | 54 | 8200 |
3x240/120 | 20.3 | 14 | 1.6 | 1.4 | 2.6 | 61 | 10570 |
3x300/150 | 22.7 | 15.5 | 1.8 | 1.4 | 2.8 | 67 | 13020 |
3x400/185 | 25.4 | 17.4 | 2 | 1.6 | 3.1 | 75 | 16560 |
Nominal Cross Section | Diameter of Conductor (Approx.) | Nominal Insulation Thickness | Nominal PVC Sheath Thickness | Overall Diameter (Approx.) | Weight of Cable (Approx.) |
mm | mm | mm | mm | mm | Kg/Km |
4x1.5 | 1.38 | 0.8 | 1.8 | 13.5 | 265 |
4x2.5 | 1.76 | 0.8 | 1.8 | 14.5 | 325 |
4x4 | 2.25 | 1 | 1.8 | 16.5 | 450 |
4x6 | 2.76 | 1 | 1.8 | 18 | 560 |
4x10 | 4 | 1 | 1.8 | 20 | 770 |
4x16 | 5 | 1 | 1.8 | 23 | 1080 |
4x25 | 6.3 | 1.2 | 1.8 | 26.5 | 1580 |
4x35 | 7.4 | 1.2 | 1.8 | 29.5 | 2070 |
4x50 | 8.8 | 1.4 | 1.8 | 34 | 2680 |
4x70 | 10.6 | 1.4 | 2 | 38 | 3760 |
4x95 | 12.4 | 1.6 | 2.1 | 44 | 4960 |
4x120 | 14 | 1.8 | 2.3 | 48 | 6110 |
4x150 | 15.5 | 1.8 | 2.4 | 53 | 7450 |
4x185 | 17.4 | 2 | 2.6 | 58 | 9220 |
4x240 | 20.3 | 2.2 | 2.8 | 65 | 11900 |
4x300 | 22.7 | 2.4 | 3 | 72 | 14730 |
4x400 | 25.4 | 2.6 | 3.3 | 81 | 18830 |
Nominal Cross Section | Diameter of Conductor (Approx.) | Nominal Insulation Thickness | Nominal PVC Sheath Thickness | Overall Diameter (Approx.) | Weight of Cable (Approx.) |
mm | mm | mm | mm | mm | Kg/Km |
5x1.5 | 1.6 | 0.8 | 1.8 | 14.5 | 300 |
7x1.5 | 1.6 | 0.8 | 1.8 | 15.5 | 360 |
10x1.5 | 1.6 | 0.8 | 1.8 | 19 | 460 |
12x1.5 | 1.6 | 0.8 | 1.8 | 19.5 | 510 |
14x1.5 | 1.6 | 0.8 | 1.8 | 20 | 570 |
19x1.5 | 1.6 | 0.8 | 1.8 | 22 | 710 |
21x1.5 | 1.6 | 0.8 | 1.8 | 23 | 770 |
24x1.5 | 1.6 | 0.8 | 1.8 | 25 | 870 |
30x1.5 | 1.6 | 0.8 | 1.8 | 26 | 1020 |
40x1.5 | 1.6 | 0.8 | 1.8 | 29 | 1290 |
48x1.5 | 1.6 | 0.8 | 1.8 | 32 | 1520 |
61x1.5 | 1.6 | 0.8 | 1.8 | 35 | 1900 |
5x1.5 | 2 | 0.8 | 1.8 | 16 | 375 |
7x2.5 | 2 | 0.8 | 1.8 | 17 | 460 |
10x2.5 | 2 | 0.8 | 1.8 | 20 | 590 |
12x2.5 | 2 | 0.8 | 1.8 | 21 | 660 |
14x2.5 | 2 | 0.8 | 1.8 | 22 | 740 |
19x2.5 | 2 | 0.8 | 1.8 | 24 | 940 |
21x2.5 | 2 | 0.8 | 1.8 | 25 | 1030 |
24x2.5 | 2 | 0.8 | 1.8 | 27 | 1150 |
HENAN UME CABLE CO., LTD has a strict quality control policy in every step from the order to After-sales service!
Production:
Q1: Are you a manufacturer?
Yes, we are the manufacturer.
Q2: What are your main products?
Our products range as follows:
1. Electrical wire/PVC Building Wires.
2. PVC/XLPE insulated Power Cables up to 110kv.
3. Overhead Aerial Bundle Cable/ABC Cables.
4. Bare Conductors, like AAC, AAAC, ACSR, ACAR, ASCR/AW, and so on.
5. Steel wire/strand-like EHS, GSW and ACS(Aluminum Clad Steel), CCS(Copper Clad Steel).
6. Rubber Cables, Mining Cables, Welding Cable, and Control Cables.
7. Concentric Cables with Copper/Aluminum/Aluminum Alloy 8000s' Conductor.
Q3: Do you provide samples? Is it free or extra?
Yes, we could offer the samples for free
Q4: Is the quality of your products guaranteed?
We have passed ISO9001, ISO14001, ISO45001, and all our products have CE certificates.
Q5: Which markets do you involve mainly in?
Our products have been exported mainly to Africa, the Middle East, Southeast Asia, South America, Central America, North America, Europe, Australia, etc.
Q6: What is your payment term?
T/T or L/C
Q7: What about the delivery time?
Generally, it is 3-7days if the goods are in stock. Or it is 7-30days if the goods are not in stock, it is according to quantity.